Total Dissolved Solids (TDS) controllers are essential devices used in various industries to monitor and regulate the concentration of dissolved solids in water. These controllers play a crucial role in ensuring water quality and preventing equipment damage caused by high TDS levels. However, the price of TDS controllers can vary significantly depending on various factors, including brand, features, and quality.
Another factor that affects the price of a TDS Controller is the features it offers. Basic TDS controllers that provide simple monitoring and control functions are typically more affordable than controllers with advanced features such as data logging, alarm systems, and remote monitoring capabilities. The additional features can enhance the performance and functionality of the controller, but they also come at a higher cost. It is essential to consider the specific needs of your application and determine which features are necessary to ensure optimal performance.
Model No. | CIT-8800 Inductive Conductivity / Concentration Online Controller | |
Measurement range | Conductivity | 0.00μS/cm ~ 2000mS/cm |
Concentration | 1.NaOH,(0-15)% or(25-50)%; | |
2.HNO3(note the Corrosion resistance of the sensor)(0-25)% or(36-82)%; | ||
3.User-defined concentration curves. | ||
TDS | 0.00ppm~1000ppt | |
Temp. | (0.0 ~ 120.0)℃ | |
Resolution | Conductivity | 0.01μS/cm |
Concentration | 0.01% | |
TDS | 0.01ppm | |
Temp. | 0.1℃ | |
Accuracy | Conductivity | 0μS/cm ~1000μS/cm ±10μS/cm |
1 mS/cm~500 mS/cm ±1.0% | ||
500mS/cm~2000 mS/cm ±1.0% | ||
TDS | 1.5 level | |
Temp. | ±0.5℃ | |
Temp. compensation | element | Pt1000 |
range | (0.0~120.0)℃ linear compensation | |
(4~20)mA Current output | channels | Double channels |
features | Isolated, adjustable, reversible, 4-20MA output, instruments/ transmitter mode. | |
Loop resistance | 400Ω(Max),DC 24V | |
Resolution | ±0.1mA | |
Control contact | Channels | Triple channels |
Contact | Photoelectric relay output | |
Programmable | Programmable ( temperature 、conductivity/concentration/TDS、timing)output | |
Features | Could set temperature、conductivity/concentration/TDS、 timing NO/NC/ PID selection | |
Resistance load | 50mA(Max),AC/DC 30V(Max) | |
Data communication | RS485,MODBUS protocol | |
Power supply | DC 24V±4V | |
Consumption | <5.5W | |
Working environment | Temperature:(0~50)℃ Relative Humidity:≤85%RH(non- condensing ) | |
Storage | Temperature:(-20~60)℃ Relative Humidity:≤85%RH(non- condensing) | |
Protection level | IP65(with rear cover) | |
Outline dimension | 96mm×96 mm×94mm (H×W×D) | |
Hole dimension | 91mm×91mm(H×W) | |
Installation | Panel mounted , fast installation |
The quality of the materials used in manufacturing the TDS Controller also plays a significant role in determining its price. Controllers made from high-quality materials that are resistant to corrosion and wear are likely to be more expensive than controllers made from lower-quality materials. Investing in a TDS Controller made from durable materials can help extend its lifespan and reduce the need for frequent replacements, ultimately saving money in the long run.
When considering the price of a TDS Controller, it is essential to weigh the cost against the performance and reliability of the device. Cheaper controllers may be more budget-friendly upfront, but they may lack the accuracy and durability needed for critical applications. On the other hand, investing in a higher-priced controller from a reputable brand with advanced features and quality materials can provide peace of mind and ensure consistent performance over time.
CCT-3300 | ||||
Constant | 10.00cm-1 | 1.000cm-1 | 0.100cm-1 | 0.010cm-1 |
Conductivity | (500~20,000) | (1.0~2,000) | (0.5~200) | (0.05~18.25) |
μS/cm | μS/cm | μS/cm | MΩ·cm | |
TDS | (250~10,000) | (0.5~1,000) | (0.25~100) | —— |
ppm | ppm | ppm | ||
Medium Temp. | (0~50)℃(Temp. Compensation : NTC10K) | |||
Resolution | Conductivity: 0.01μS/cm;0.01mS/cm | |||
TDS: 0.01ppm | ||||
Temp.: 0.1℃ | ||||
Accuracy | Conductivity:1.5%(FS) | |||
Resistivity: 2.0%(FS) | ||||
TDS:1.5%(FS) | ||||
Temp:±0.5℃ | ||||
Analog Output | Single isolated(4~20)mA,instrument/transmitter for selection | |||
Control Output | SPDT relay,Load Capacity: AC 230V/50A(Max) | |||
Working Environment | Temp: (0~50)℃;Relative humidity: ≤85%RH(none condensation) | |||
Storage Environment | Temp:(-20~60)℃; Relative humidity ≤85%RH(none condensation) | |||
Power Supply | DC 24V/AC 110V/AC 220V±15%(for selection) | |||
Dimension | 48mm×96mm×80mm (H×W×D) | |||
Hole Size | 44mm×92mm (H×W) | |||
Installation | Panel mounted, fast installation |